Subject: Who can help settle a bet??
From: sasha@icanect.net (sasha)
Date: Tue, 05 Nov 1996 00:20:15 GMT
This is the subject of a friendly debate between a good friend of
mine, who happens to be
a plumber and myself.(not a plumber)
I'm not sure if I posted this in the best newsgroup but it is the
educated mind of a engineer
that can settle this question in hydraulics.
Lets assume, that you have a perfectly functional and working lawn
sprinkler system,
powered by a electric moter. If you could snap your fingers and all
horizontal conduits
were now eight inches in diameter, how would the increse in conduit
size effect the
performance of the system?
I say, that since water is uncompresable, the pump will be supplying
the same volume of
water to the spray heads, and that the larger pipe size actually means
less hydraulic
resistence and the system might even be improved. It is the pump that
determines the
pressure in the system with a given amount of flow determined by the
spray heads
Plumber says, that the pump will have a harder time pumping the extra
amount of heavy
water, and that the back pressure created by the greater resistence in
the smaller conduits
is needed to keep the pressure at the spray heads
Is there a engineer out there that can put an end to this
debate???????
Sasha.
Subject: Re: Who can help settle a bet??
From: Minstrel
Date: Mon, 04 Nov 1996 22:15:02 -0500
sasha wrote:
>
> This is the subject of a friendly debate between a good friend of
> mine, who happens to be
> a plumber and myself.(not a plumber)
>
>
> I'm not sure if I posted this in the best newsgroup but it is the
> educated mind of a engineer
> that can settle this question in hydraulics.
>
THis is the right newsgroup...
> Lets assume, that you have a perfectly functional and working lawn
> sprinkler system,
> powered by a electric moter. If you could snap your fingers and all
> horizontal conduits
> were now eight inches in diameter, how would the increse in conduit
> size effect the
> performance of the system?
>
> I say, that since water is uncompresable, the pump will be supplying
> the same volume of
> water to the spray heads, and that the larger pipe size actually means
> less hydraulic
> resistence and the system might even be improved. It is the pump that
> determines the
> pressure in the system with a given amount of flow determined by the
> spray heads
>
> Plumber says, that the pump will have a harder time pumping the extra
> amount of heavy
> water, and that the back pressure created by the greater resistence in
> the smaller conduits
> is needed to keep the pressure at the spray heads
>
> Is there a engineer out there that can put an end to this
> debate???????
>
> Sasha.
Plumber's right... I'd be able to prove it since I had a project back in
college that dealt with the design on a sprinkler tube, and it is the
pressure that pushes the water out of the little holes.
Plus, if you're keeping the same pump with the increased pipe ID, the
pump won't work as efficiently, and there would be less pressure inside
the piping. It all has to do with pump curves and system curves.
As I said, I did a project similar to this back in Fluids 1... I'd
explain it better, but I have a bugger of a headache right now... and I
can't find my project work... *shrug*
If someone can corroborate (sp?) this, most appreciated...
Minstrel
--
Adam Johnson BlackWing
tengu@concentric.net Minstrel
http://www.concentric.net/~tengu/
"Well did you ever get the feeling that the story's too damned real
and in the present tense?
Or that everybody's on the stage and it seems like you're the only
person sitting in the audience?"
--- Jethro Tull, "Skating Away on the Thin Ice
to a New Day"
Subject: Re: Who can help settle a bet??
From: John Moffat
Date: Tue, 05 Nov 1996 12:45:44 +0000
sasha wrote:
>
> Lets assume, that you have a perfectly functional and working lawn
> sprinkler system,
> powered by a electric moter. If you could snap your fingers and all
> horizontal conduits
> were now eight inches in diameter, how would the increse in conduit
> size effect the
> performance of the system?
>
> I say, that since water is uncompresable, the pump will be supplying
> the same volume of
> water to the spray heads, .....
>
> Plumber says, that the pump will have a harder time pumping the extra
> amount of heavy
> water, ....
On balance I'd say that you were more correct than the plumber.
The increase in diameter - provided the fluid flow in the pipes remains
turbulent - will reduce the pressure drop in the system and more flow rate will
be able to be passed by the pump.
Provided there is no increase in the vertical height of the pipes, the effective
"weight" of the water at the pump outlet will remain the same.
The statement that "the back pressure in the pipes is needed .." is not true.
The pressure at the pump is maintained by the header pressure which, presumably
will remain unchanged in the system. The flow rate thru the sprinkler is
governed by the outlet pressure from the pump minus the line loss and divided
by the sprinkler's loss coefficient (a function of hole size, X-sectional area
etc..). Clearly any reduction in line loss will mean more flow thru the
sprinkler - on top of the gain in flow rate from improved pump performance.
Subject: Re: Who can help settle a bet??
From: charliew@hal-pc.org (charliew)
Date: Tue, 05 Nov 96 13:42:10 GMT
In article <327EB136.182D@concentric.net>,
Minstrel wrote:
>sasha wrote:
>>
>> This is the subject of a friendly debate between a good
friend of
>> mine, who happens to be
>> a plumber and myself.(not a plumber)
>>
>>
>> I'm not sure if I posted this in the best newsgroup but
it is the
>> educated mind of a engineer
>> that can settle this question in hydraulics.
>>
>
>THis is the right newsgroup...
>
>
>> Lets assume, that you have a perfectly functional and
working lawn
>> sprinkler system,
>> powered by a electric moter. If you could snap your
fingers and all
>> horizontal conduits
>> were now eight inches in diameter, how would the increse
in conduit
>> size effect the
>> performance of the system?
>>
>> I say, that since water is uncompresable, the pump will
be supplying
>> the same volume of
>> water to the spray heads, and that the larger pipe size
actually means
>> less hydraulic
>> resistence and the system might even be improved. It is
the pump that
>> determines the
>> pressure in the system with a given amount of flow
determined by the
>> spray heads
>>
>> Plumber says, that the pump will have a harder time
pumping the extra
>> amount of heavy
>> water, and that the back pressure created by the greater
resistence in
>> the smaller conduits
>> is needed to keep the pressure at the spray heads
>>
>> Is there a engineer out there that can put an end to this
>> debate???????
>>
>> Sasha.
>
>Plumber's right... I'd be able to prove it since I had a
project back in
>college that dealt with the design on a sprinkler tube, and
it is the
>pressure that pushes the water out of the little holes.
>Plus, if you're keeping the same pump with the increased
pipe ID, the
>pump won't work as efficiently, and there would be less
pressure inside
>the piping. It all has to do with pump curves and system
curves.
>
>As I said, I did a project similar to this back in Fluids
1... I'd
>explain it better, but I have a bugger of a headache right
now... and I
>can't find my project work... *shrug*
>If someone can corroborate (sp?) this, most appreciated...
>
>Minstrel
>
>
I'd say that you better do the college project again.
Almost all of the pressure drop will be taken at the
sprinkler nozzles (where the water comes out), as these
nozzles are very small orifices compared to the diameter of
the piping that supplies them. Increasing the piping
diameter of the pipe going to the sprinkler will
theoretically decrease the pressure drop in the system
upstream of the sprinkler, leading to a higher pressure at
the sprinkler (not lower). However, it is likely that the
sprinkler takes 90-95% of the pressure drop in this system.
Thus, while it is theoretically correct to increase piping
diameter for the sake of efficiency, you will see little or
no practical increase as a result.
Regarding the effect on the pump, it will continue to see
approximately the same flow rate. Since the pump discharge
pressure will remain more or less the same, assuming a
centrifugal pump (see curve of discharge pressure vs. flow
rate, if it exists), the pump's driver should use about the
same amount of energy as before. In other words, there will
be a slight improvement in the sprinkler system efficiency
(slightly more water flow), but if you try to measure it,
you will not be able to detect a significant difference
unless the original piping diameter upstream of the
sprinkler is very small.
On purely theoretical grounds, Sasha wins the bet.
===================================================================
For some *very* interesting alternate viewpoints, look at
http://www.hamblin.com/mf.main/welcome.html
Subject: Job Opening: Engineer/programmer for heat transfer/fluid flow code development
From: crtech@netcom.com (Brent Cullimore)
Date: Tue, 5 Nov 1996 22:27:20 GMT
C&R; Technologies has an immediate opening for an engineering/programmer to
support development advanced versions of our SINDA/FLUINT thermal/hydraulic
network analyzer.
Job Description ------------------------------------------------------------
Primary job responsibilities are the expansion of the existing SINDA/FLUINT
code (written in Fortran and C/C++) to include noncondensible gas dissolution/
evolution and full nonequilibrium two-phase duct flow.
Secondary activities include customer support and training, consulting,
validation/verification, and user documentation support.
ESSENTIAL: - BS in engineering, especially mechanical or chemical
- 5+ years work experience
- extensive knowledge of hydraulics and pipe flow
- extensive experience in numerical analysis programming
using Fortran, C or C++
- strong work ethic: self-motivating and self-supervising
- strong English communications skills
PLUSES: - MS in engineering, especially mechanical or chemical
- 10+ years work experience
- knowledge of two-phase flow and mixture thermodynamics
- experience using SINDA/FLUINT
- programming experience in C and/or C++
- usage/programming experience in automated design optimization
- usage/programming experience in 2D/3D CFD
- foreign languages
Company Information --------------------------------------------------------
C&R; Technologies is a rapidly expanding engineering software and consulting
company located near Denver, Colorado. Our specialties are heat transfer and
fluid flow system design and analysis. For more details on our existing
software products, see http://www.webcom.com/crtech
----------------------------------------------------------------------------
Please e-mail or snail-mail resumes WITH REFERENCES to:
C&R; Technologies
Attn: Personnel
49 Dawn Heath Circle
Littleton CO 80127
crtech@netcom.com Please put "Attn: Personnel" in the subject.
Text, Postscript, FrameMaker preferred.
Word, AmiPro, HTML accepted.
If you have sent us your resume previously, please send a fresh copy
referencing the current job opening: "FLUINT Programmer."
--
_______
_____ \| \\
// \| || || Cullimore and Ring Technologies, Inc.
|| | ||___// 49 Dawn Heath Circle
|| || \\ Littleton Colorado 80127-4303
|| || \\ (303) 971-0292 crtech@netcom.com
\\ || \\ http://www.webcom.com/crtech >
========================================================================== >
Thermal/Fluid System Design and Analysis >